TECHNICAL DATA:
FABRIC
FABRIC PRODUCT DESCRIPTION: Safe-T-Guard is a non-hazardous, non-toxic interior flame retardant for most fibers including synthetics and metallic. Also works wonderful on cardboard and paper. If applied properly, this product will not leave a white flaky residue behind. In most cases, this product will not change the hand of the fabric, will not dis-color or shrink the fabric. No smell and easy to apply on or off-site. When choosing fibers to flame-retard, the most difficult fibers are acrylic, acetate and some nylons. Although pre-testing is recommended for all fibers, these fibers most definitely need to be pre-tested. Can be dried with heat up to 300º. May need up to a 24 hour cure time depending upon application process and substrate.
APPROVALS:
 |
For Fabric: |
 |
CAN/ULC-S109-03 Large-Flame Test |
 |
California Chemical Approval #C-10002 |
 |
NFPA 701, small and large scale; NFPA 701, Test No. 1, |
 |
CA Title 117 |
 |
CA Title 19, |
 |
New York City Administrative Code §27-4266 and 3RCNY §19-01, Public Safety Section 1237, |
 |
FAA 25,853B, BFD IX-1, MVSS302, State of Massachusetts, Boston Fire Code, |
 |
British Standard 5867: Part2:1987 |
 |
New York Port Authority, Has been approved by ICBO, |
 |
City of L.A. TB-603, NFPA 285. |
|
 |
For Wood: |
 |
Meets ASTM E-84, UL 723, UBC No. 42y, NFPA 255, Class II flame spread rating, California Chemical Approval #C-10002, ICBO #3656, City of L.A. Approval No. 24303. |
 |
British Standard 476:Part 7:1987 |
|
|
| Toxicity reports available upon request. |
TESTING PROCEDURES: Safe-T-Guard Flame Retardant is ready to use. Applicator should wear chemical gloves, goggles and a respirator. Follow all fire safety precautions and test at your own risk. All items to be treated must be tested for verification of chemical amount, appearance, texture and performance results. Safe-T-Guard Flame Retardant will perform best if no other coating such as water repellent is on the surface. Cut two strips of specimen samples long enough for testing. Using a Hudson type orchard sprayer, apply at 40-60 PSI using a fan spray tip. Apply the chemical on one side of the first specimen and label. On the second specimen, apply the chemical on both sides and label. Let dry and cure for 3-72 hours, (average is 3-24 hours) and test. NFPA 705, Field Flame Testing Procedures are recommended for testing, although it does not guarantee acceptance by the fire authority. If results are not satisfactory, an additional light spray may be repeated or additional curing time may be required.
APPLICATION PROCEDURES: User should determine the suitability of this flame retardant for its intended use. Safe-T-Guard is ready to use and must be applied cautiously. Applicator should wear chemical gloves, goggles and a respirator. Safe-T-Guard flame retardant will cover 200-800 square feet depending upon the fiber content of the item being treated. Using a Hudson type orchard sprayer, apply at 40-60 PSI using a fan spray tip, spray entire area and cover completely. Testing results will determine chemical amount and cure time. Certification requires application by a California State Certified Applicator to comply with requirements of the California State Fire Marshal.
Users of this product must determine the suitability of this product for its intended use.
Application Instructions for Fabric
For Fabric: Safe-T-Guard is ready to use and must be applied cautiously. Applicator should wear chemical gloves, goggles and a respirator. Safe-T-Guard will cover 200-800 square feet depending upon the fiber content of the item being treated. Using a Hudson type orchard sprayer, apply at 40-60 PSI using a fan spray tip, spray entire area and cover completely. Testing results will determine chemical amount and cure time. Certification requires application by a California State Certified Applicator to comply with requirements of the California State Fire Marshal.
Application Instructions Wood
WOOD PRODUCT DESCRIPTION: Safe-T-Guard flame retardant is a non-hazardous, non-toxic, interior class B flame-retardant saturant for wood.
APPROVALS: Meets ASTM E-84, UL 723, UBC No. 42y, NFPA 255, Class II flame spread rating, California Chemical Approval #C-10002, ICBO #3656, City of L.A. Approval No. 24303.
APPLICATION PROCEDURES: Before using, user should determine the suitability of this product for its intended use. Ready to use. Applicator should wear chemical gloves, goggles and respirator. All wood must be free from coatings such as paint, sealant or dirt. Coverage is 250 square feet per gallon. Using a hand Hudson type orchard sprayer, apply at 40-60 PSI using a fan spray tip, spray entire area and cover completely. he state of CA requires application by a CA Certified Applicator to obtain documented certification.
Application Instructions Cardboard and Paper
Due to various thickness of cardboard and paper, proper testing will determine application procedures.
GENERAL INFORMATION FOR FABRIC AND WOOD
CLEAN-UP: Flush sprayer and tips with warm water and wash hands with soap and water.
CAUTION: Keep out of reach of children. Do not ingest. Call physician if swallowed. Clean with soap and water all contacted areas. Flush eyes with chemical eye wash or flush eyes with cool water for at least 15 minutes. If irritation persists seek advice of a Physician. |